F-Gas English Low GWP

Minden kérdés
HFC | Flammable | CO₂ | NH₃
Könnyű kérdések | Közepes nehézségű kérdések | Nehéz kérdések

1

Nehéz

What additional protective equipment will you use when soldering systems containing HC refrigerants?


Tinted safety goggles
High-visibility jacket
Flammable gas detector
Fire blanket

2

Nehéz

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


The pressure switch setting will not be correct
There is a risk of refrigerant leakage
It is a potential source of ignition
Dust and moisture may enter

3

Nehéz

What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?


3 m
2 m
0.5 m
1 m

4

Nehéz

What is the maximum safe charge for a recovery cylinder with R32 refrigerant, if it can be charged with 20 kg of R410A?


20 kg
33 kg
9 kg
18 kg

5

Nehéz

According to EN 378, what is the maximum charge of an A3 refrigerant for a display unit (hermetic, with an internal condenser) located in the ground-floor retail area of a supermarket?


10 kg
1.0 kg
2.5 kg
1.5 kg

6

Nehéz

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Use an ATEX-certified vacuum pump in a well-ventilated area
There is no need to evacuate such systems
Fit a long hose to the pump outlet to remove HC away from the system
Position the vacuum pump 3 metres above floor level

7

Nehéz

What protective equipment must you have in your car when transporting flammable substances?


Tinted safety goggles
A fire extinguisher
Thick gloves
Fire blanket

8

Nehéz

How would you remove the refrigerant from a 10kg R32 water chiller, located outdoors, before unsoldering the connections?


Vent the R32 to the outside; charge the system with nitrogen until an overpressure is achieved, vent and drain the system twice, charge the system with nitrogen a third time and vent
Vent the R32 to the outside and drain the system
Recover the R32 until a vacuum is achieved
Recover the R32 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g

9

Nehéz

Which of the following leak detection methods cannot be used to locate an HC refrigerant leak?


Soapy water solution
Leak detection foam
Electronic leak detector for flammable refrigerants
Electronic HFC leak detector

10

Nehéz

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


Different low-pressure switch setting
A flammable refrigerant recovery unit has no ignition sources
A different colour for the station
Different connection sizes

11

Nehéz

Which of the following is a source of ignition?


Contactor
Defrost heating element
Ex-certified evaporator fan motor
‘n’ type thermostat

12

Nehéz

What substance is produced when R32 is burnt?


Hydrochloric acid
Phosgene
Carbon monoxide
Hydrogen fluoride

13

Nehéz

What type of refrigerant is R1234ze?


Hydrochlorofluoro-hydrocarbon
Hydrocarbon
Hydrofluoroolefin
Chloro-fluoro-hydrocarbon

14

Nehéz

What hazards does a Group A3 refrigerant pose?


High toxicity, high flammability
Low toxicity, moderate flammability
High toxicity, moderate flammability
Low toxicity, highly flammable

15

Nehéz

According to EN 378, what is the maximum charge of R290 in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R290 is 0.038 kg/m³)?


1.5 kg
1.0 kg
4.93 kg
0.285 kg

16

Nehéz

What is the cooling capacity of R32 compared to R410A?


130%
60%
75%
105%

17

Nehéz

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


Because they must be kept running continuously to disperse the leaking refrigerant
Because they are more energy-efficient
To avoid a source of ignition in the event of a flammable refrigerant leak
Because they are more reliable

18

Nehéz

Why is the difference in density between HC and HFC refrigerants important?


Because it affects the charge weight
Because it affects the charging rate
Because it affects energy efficiency
Because it increases operating pressures

19

Nehéz

What is the GWP value for R290?


7
675
3
A. 0.02

20

Nehéz

Which of the following is not a source of ignition?


Electrical switch
An Ex-certified fan motor
Light switch
Open mechanical pressure switch

21

Nehéz

What is R290?


Propylene
Butane
Propene
Propene

22

Nehéz

According to EN 378, what is the maximum HC refrigerant charge for a display unit (hermetic system with an internal condenser) located in the ground-floor shopping area of a supermarket?


1.5 kg
1.0 kg
2.5 kg
150 g

23

Nehéz

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


Current consumption differs for compressors using flammable refrigerants compared to those using HFCs
It could be a source of ignition
A relay is never required for compressors using flammable refrigerants
The method of starting the compressor motor differs from that used with HFCs

24

Nehéz

What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?


10 m
1 m
5 m
3 m

25

Nehéz

What is the safe charge for a recovery cylinder with R290 refrigerant, if it can be charged with 10 kg of R404A?


3.6 kg
20 kg
8 kg
17 kg

26

Nehéz

How can a vacuum pump be used safely to evacuate a system containing R290?


There is no need to evacuate systems containing R290
Fit a long hose to the pump outlet to remove HC away from the system
Position the vacuum pump 3 metres above floor level
Use an ATEX-certified vacuum pump in a well-ventilated area

27

Nehéz

In accordance with ADR regulations, what protective equipment must you have in your vehicle when transporting flammable refrigerants?


Tinted safety goggles
Fire blanket
Thick gloves
A fire extinguisher

28

Nehéz

How do you ensure it is safe to light the torch needed to desolder joints in a system that has been evacuated of flammable refrigerant?


Work outdoors
You must not desolder joints on a system containing a flammable refrigerant; they must be cut using a pipe cutter
Ensure the area is well ventilated and use a flammable gas detector to check the area
Purge the system with oxygen-free nitrogen

29

Nehéz

How would you remove the refrigerant from a system containing 100 g of R1270 so that it is ready for the joints to be desoldered?


Recover the R1270 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g
Vent the R1270 to the outside; charge the system with nitrogen until an overpressure is reached, vent and evacuate the system twice, charge the system with nitrogen a third time and vent
Vent the R1270 to the outside and drain the system
Recover the R1270 until a vacuum is achieved

30

Nehéz

Which of the following leak detection methods cannot be used to locate a leak of R290 refrigerant?


Electronic leak detector for flammable refrigerants
Leak detection foam
Fluorescent dye and a UV lamp
Electronic HFC leak detector

31

Nehéz

Why can’t recovery stations designed for HFCs be used with R600a?


The recovery unit cannot withstand the working pressure of R600a
The oil in the recovery unit is not soluble in R600a
It contains ignition sources
The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure

32

Nehéz

According to EN 378, what is the maximum charge of R1234ze in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R1234ze is 0.303 kg/m³)?


6.18 kg
227 kg
618 kg
2.27 kg

33

Nehéz

What type of refrigerant is R32?


Hydrocarbon
Hydrofluorocarbon
Carbon dioxide
Hydrofluoroolefin

34

Nehéz

What hazards do A2L refrigerants pose?


Low toxicity, high flammability
Low toxicity, moderate flammability
High toxicity, moderate flammability
High toxicity, high flammability

35

Nehéz

What danger is associated with the combustion of HFO or HFC refrigerants?


Hydrogen fluoride is produced
Citric acid is produced
Phosgene is produced
Nitrous oxide is produced

36

Nehéz

What is the approximate displacement volume required for a compressor running on R600a compared to one running on R134a to achieve the same cooling capacity?


Half
The same
Twice
Seven times

37

Nehéz

What is the GWP value for R32?


7
675
3
0

38

Nehéz

Why is the accuracy of the charge weight more important for systems critically charged with R290 compared to those using HFCs


Because R290 is only used in systems with a charge of less than 150g
Because these systems never have liquid receivers
The charge mass is significantly lower than in an HFC system, as the density is much lower
Due to lower operating pressures

39

Nehéz

Why does the condenser fan run continuously in some systems using R1270?


To ensure that the discharge pressure never becomes excessive
To dilute the refrigerant in the event of a leak
To prevent the build-up of contaminants in the condenser
To reduce energy consumption

40

Nehéz

What must be included on the label of a cylinder containing a flammable refrigerant?


Agent name only
The name of the refrigerant, the hazard symbol and basic safety information
Net weight only
Information about the cylinder owner

41

Nehéz

Why does the absence of a ‘flammable agent’ label on the system pose a significant hazard?


It has no significant impact on safety
It may lead to the use of tools that are a source of ignition
It reduces the system’s efficiency
It may lead to the incorrect selection of oil

42

Nehéz

Which set of information on the label of a flammable agent cylinder is crucial from a safety perspective?


Gross weight and batch number
Manufacturer’s name and country of origin
Cylinder colour and date of manufacture
Name of the substance, hazard pictogram, UN number

43

Nehéz

What is the requirement regarding the labelling of an installation containing a flammable substance?


Colour-coding of pipes is sufficient
Labelling is required only in technical rooms
The labelling must indicate the type of substance and the flammability hazard
Labelling is not required for hermetically sealed systems

44

Nehéz

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


Merely a reduction in efficiency
Merely installation difficulties
Risk of leakage and the formation of an explosive mixture
No impact on safety

45

Nehéz

What is the purpose of installing gas detectors in a room with a refrigeration system?


Monitoring pipe pressure
Regulating compressor capacity
Measuring the refrigerant temperature
Early detection of refrigerant leaks and prevention of health risks

46

Nehéz

How often should gas detection sensors in the service room be checked?


Once every 5 years
In accordance with the manufacturer’s instructions and applicable health and safety regulations
Before each start-up of the unit
Only after a leak has occurred

47

Nehéz

Where should a gas detector be positioned in accordance with EN 378?


On the ceiling if the gas is lighter or heavier than air; near the floor if it is lighter or heavier
Near the control panel
Only at the entrance to the room
Anywhere in the room

48

Nehéz

How should an employee respond when a gas alarm is triggered?


Reduce the pressure in the system
Carry on working until they see a leak
Leave the room immediately and notify their supervisor
Switch off the system and wait for the alarm to stop

49

Nehéz

What safety checks should be carried out when installing a new refrigeration system?


The presence of health and safety signage, adequate ventilation and gas detectors
Is the air filter new?
Only the compressor power
The colour of pipes and hoses

50

Nehéz

Gas detectors should be installed in rooms where:


Any refrigerant is present, regardless of the quantity
The room is less than 5 m²
Ventilation is natural
The amount of refrigerant exceeds a specified permissible threshold

51

Nehéz

What is the minimum number of emergency exits in a plant room (refrigeration plant room) and how should they be signposted?


At least two exits, but signage is optional
One exit, clearly marked in the direction of escape
One exit with an information sign about the refrigerant
Exits do not need to be signposted if the room is small

52

Nehéz

Which measure, when installing a system using a flammable refrigerant, improves its energy efficiency?


Increasing the refrigerant charge
No leak test
Restriction of ventilation
Thorough leak testing and vacuuming

53

Nehéz

How do leaks affect systems using flammable refrigerants?


They cause refrigerant loss, reduced efficiency and a fire hazard
Have no effect
They lower the temperature
They improve efficiency

54

Nehéz

Why is it important to limit the amount of refrigerant in HC systems?


It lowers the temperature
It increases efficiency
It has no effect
It reduces the risk of explosion and improves the system’s operational safety

55

Nehéz

Why is the cleanliness of heat exchangers in HC systems important?


It improves heat transfer and reduces energy consumption
It doesn’t matter
It increases the pressure
Causes leaks

56

Nehéz

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Disabling safety devices
Regular checks for leaks and operating parameters
Increasing the refrigerant charge
Lack of servicing

57

Nehéz

How does the correct selection of components affect a system using a flammable refrigerant?


It ensures safe and optimal operation and minimises energy losses
It doesn’t matter
It increases the amount of refrigerant
It lowers the temperature

58

Nehéz

Why is it important to use the correct service tools in HC systems?


It increases energy consumption
Causes leaks
It ensures operational safety and reduces refrigerant losses
It doesn’t matter

59

Nehéz

How does pipe insulation affect the efficiency of systems containing HC?


It doesn’t matter
It increases the pressure
It reduces energy losses and improves efficiency
Causes leaks

60

Nehéz

What hazards are associated with a Class A3 safety agent?


High toxicity, does not propagate flames
Slightly flammable, lower toxicity
High flammability, lower toxicity
Lower toxicity, does not propagate flames

61

Nehéz

18 What is the GWP of R32 (according to AR4)?


675
6
3945
0

62

Nehéz

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Lower flammability limit, room volume
Practical limit, room volume
Lower flammability limit, height of the indoor unit, floor area
Practical limit, height of the indoor unit, floor area

63

Nehéz

What compressor displacement is required for R1270, relative to R404A compressors for the medium-temperature range (cold store)?


Similar
150%
600%
50%