F-Gas English Low GWP

Minden kérdés
HFC | Flammable | CO₂ | NH₃
Könnyű kérdések | Közepes nehézségű kérdések | Nehéz kérdések

1

Nehéz

What is the main difference between a dry evaporator and a flooded evaporator?


A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator
A dry evaporator has a lower operating pressure than a flooded one
A dry evaporator does not require an expansion valve, whereas a flooded one does
A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas

2

Nehéz

What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?


A pressure varying between 10 and 20 bar
Atmospheric pressure, approximately 1 bar
Positive pressure, in the range of 5–10 bar
Negative pressure (vacuum), below 0 bar

3

Nehéz

Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?


They are readily biodegradable, so they only pollute the environment for a short time
They are persistent, accumulate in the environment and may be toxic
They cause rapid cooling of the atmosphere
They are climate-neutral

4

Nehéz

What is the basic requirement when charging a system with R717 (NH₃)?


NH₃ can be charged together with air
Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging must only take place at temperatures below 0°C
Charging can be carried out without personal protective equipment

5

Nehéz

How should oil be handled in systems using R717?


Oil can be mixed with any refrigerant
The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks
Oil has no effect on the system’s operation
The oil does not require any monitoring

6

Nehéz

What is the correct procedure for recovering R717 from a system?


Recovery is not required
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The refrigerant can be drained into the sewer system
The gas can be released into the atmosphere

7

Nehéz

How should R717 (NH₃) be stored?


In any open containers
Near heat sources
In sealed, labelled containers, in a cool and well-ventilated place
In unmarked plastic containers

8

Nehéz

What should be done in the event of R717 contamination?


Add water to dilute it
Release into the atmosphere
The refrigerant must be purified or sent for disposal in accordance with regulations
Continue to use without restriction

9

Nehéz

What is the main hazard associated with an R717 leak during maintenance work?


Increased cooling efficiency
No risk whatsoever
Toxic to humans and may cause chemical burns
Damage to electrical equipment only

10

Nehéz

What action should be taken if an NH₃ leak is detected?


Increase the pressure in the system
Ignore it and carry on working
Close your eyes and carry on working
Evacuate personnel immediately and remove the source of the leak, if it is safe to do so

11

Nehéz

What role do scrubbers play in NH₃ systems?


Neutralises ammonia through absorption in a liquid (e.g. water)
They increase the pressure in the system
They store the refrigerant
They are used to measure temperature

12

Nehéz

How should the system be prepared before filling with R717?


Check for leaks, remove air and moisture, and create a vacuum
There is no need to check it
The pressure must be increased above the standard level
Simply start it up

13

Nehéz

What are the transport requirements for R717?


It can be transported in open containers
It can be transported without labelling
Must be transported in suitable, labelled containers in accordance with ADR regulations
Transport is not subject to regulations

14

Nehéz

What personal protective equipment is required when working with NH₃?


Workwear only
Only a safety helmet
Safety goggles, gloves and respiratory protective equipment
No requirements

15

Nehéz

Which statement best describes the behaviour of R717 and mineral compressor oil?


In an R717 system, a return oil line cannot be used because the oil is too hot
R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717
R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717
R717 mixes very well with compressor oil and easily returns to the compressor

16

Nehéz

Which system may require manual oil recovery?


Supercritical ‘booster’ system using R744
Secondary system using R744
R744 cascade system
An R717 system

17

Nehéz

Which refrigerant is lighter than air?


R744
R1234ze
R1270
R717

18

Nehéz

R717 is highly corrosive to


aluminium
copper
titanium
stainless steel

19

Nehéz

What is the effect of repeatedly opening the relief valve?


The valve remains fully open continuously
The relief pressure drops
The valve will not open
The relief pressure rises

20

Nehéz

What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?


P2 = T2/(P1 × T1)
P2 = (P1 × T1)/T2
P2 = T1/(P1 × T2)
P2 = (P1 × T2)/T1

21

Nehéz

What is the recommended alarm level for fixed leak detection systems for R717?


500 ppm
50,000 ppm
5,000 ppm
500,000 ppm

22

Nehéz

Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?


Because compressors with a separate motor are cheaper
Because NH₃ reacts with the motor windings and hermetic compressors are not used
To reduce the condensing pressure
To increase the amount of refrigerant in the system

23

Nehéz

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Diaphragm compressor
Rotary vane compressor
Hermetic scroll

24

Nehéz

How is the capacity of a piston compressor regulated in NH₃ systems?


By reducing the refrigerant charge
By unloading the cylinders or changing the rotational speed
Solely by adjusting the oil volume
By increasing the condensing pressure

25

Nehéz

How is the capacity of a screw compressor most commonly controlled?


By changing the type of oil
By using a slide valve
By adjusting the oil level
By closing the suction valve

26

Nehéz

When is two-stage compression used in NH₃ systems?


At small temperature differences
Only with water-cooled condensers
At very low vapour pressures and high pressure differentials
Exclusively in small systems

27

Nehéz

What is the advantage of two-stage compression over single-stage compression?


No need for a separator
Higher efficiency and lower discharge temperature
Higher energy consumption
Lower efficiency

28

Nehéz

How does an evaporative condenser used in NH₃ systems work?


Operates without a fan
It transfers heat only to the air
It utilises the evaporation of water to increase cooling efficiency
It does not require a water supply

29

Nehéz

What is the function of the liquid separator in an NH₃ system?


It prevents liquid from entering the compressor
Regulates the condensing pressure
Increases the discharge temperature
It separates oil from the refrigerant

30

Nehéz

What is the purpose of monitoring the liquid level in the separator?


To control the condenser fan
To increase the oil volume
To maintain the correct refrigerant level and prevent the compressor from flooding
To reduce the condensing temperature

31

Nehéz

What is the role of the float switch in NH₃ systems?


It controls the fan’s operation
It is used to detect leaks
It monitors the liquid level in the tank or separator
It regulates the condensation temperature

32

Nehéz

What is a thermosiphon in NH₃ systems?


A defrosting device
A type of safety valve
A type of evaporator
An oil circulation system utilising differences in pressure and temperature

33

Nehéz

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To increase the amount of refrigerant
Because the oil mixes only with water
Because NH₃ does not mix with most compressor oils
To reduce the pressure

34

Nehéz

What is the main function of an oil separator in NH₃ systems?


To lower the condensation temperature
To increase fan efficiency
Removing moisture from the system
To separate the oil from the refrigerant and return the oil to the compressor

35

Nehéz

Which NH₃ system features direct evaporation of the refrigerant in the evaporator?


Indirect system
Direct expansion (DX) system
Thermosiphon system
Glycol system

36

Nehéz

What is the characteristic feature of a flooded evaporator system?


No level control is required
No separator is used
The evaporator is filled exclusively with vapour
The evaporator contains a large amount of liquid, which improves heat transfer

37

Nehéz

What is the main difference between a direct and an indirect system?


In a direct system, there is no evaporator
In an indirect system, no compressor is used
In an indirect system, NH₃ flows directly into the space being cooled
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load