F-Gas English Low GWP

All questions
HFC | Flammable | CO₂ | NH₃
Easy questions | Medium questions | Difficult questions

1

Difficult

What additional protective equipment will you use when soldering systems containing HC refrigerants?


Tinted safety goggles
Flammable gas detector
High-visibility jacket
Fire blanket

2

Difficult

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


The pressure switch setting will not be correct
There is a risk of refrigerant leakage
Dust and moisture may enter
It is a potential source of ignition

3

Difficult

What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?


2 m
1 m
0.5 m
3 m

4

Difficult

What is the maximum safe charge for a recovery cylinder with R32 refrigerant, if it can be charged with 20 kg of R410A?


18 kg
20 kg
9 kg
33 kg

5

Difficult

According to EN 378, what is the maximum charge of an A3 refrigerant for a display unit (hermetic, with an internal condenser) located in the ground-floor retail area of a supermarket?


1.5 kg
10 kg
2.5 kg
1.0 kg

6

Difficult

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Fit a long hose to the pump outlet to remove HC away from the system
Position the vacuum pump 3 metres above floor level
Use an ATEX-certified vacuum pump in a well-ventilated area
There is no need to evacuate such systems

7

Difficult

What protective equipment must you have in your car when transporting flammable substances?


Thick gloves
Tinted safety goggles
A fire extinguisher
Fire blanket

8

Difficult

How would you remove the refrigerant from a 10kg R32 water chiller, located outdoors, before unsoldering the connections?


Vent the R32 to the outside; charge the system with nitrogen until an overpressure is achieved, vent and drain the system twice, charge the system with nitrogen a third time and vent
Vent the R32 to the outside and drain the system
Recover the R32 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g
Recover the R32 until a vacuum is achieved

9

Medium

What is R1270?


Propene
Butane
Isobutane
Propene

10

Difficult

Which of the following leak detection methods cannot be used to locate an HC refrigerant leak?


Soapy water solution
Electronic HFC leak detector
Leak detection foam
Electronic leak detector for flammable refrigerants

11

Difficult

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


Different low-pressure switch setting
A different colour for the station
A flammable refrigerant recovery unit has no ignition sources
Different connection sizes

12

Difficult

Which of the following is a source of ignition?


Contactor
‘n’ type thermostat
Defrost heating element
Ex-certified evaporator fan motor

13

Difficult

What substance is produced when R32 is burnt?


Carbon monoxide
Hydrogen fluoride
Hydrochloric acid
Phosgene

14

Difficult

What type of refrigerant is R1234ze?


Chloro-fluoro-hydrocarbon
Hydrochlorofluoro-hydrocarbon
Hydrofluoroolefin
Hydrocarbon

15

Difficult

What hazards does a Group A3 refrigerant pose?


High toxicity, moderate flammability
Low toxicity, highly flammable
High toxicity, high flammability
Low toxicity, moderate flammability

16

Difficult

According to EN 378, what is the maximum charge of R290 in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R290 is 0.038 kg/m³)?


1.0 kg
4.93 kg
1.5 kg
0.285 kg

17

Difficult

What is the cooling capacity of R32 compared to R410A?


60%
130%
75%
105%

18

Difficult

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


To avoid a source of ignition in the event of a flammable refrigerant leak
Because they are more reliable
Because they must be kept running continuously to disperse the leaking refrigerant
Because they are more energy-efficient

19

Difficult

Why is the difference in density between HC and HFC refrigerants important?


Because it increases operating pressures
Because it affects the charging rate
Because it affects energy efficiency
Because it affects the charge weight

20

Difficult

What is the GWP value for R290?


7
A. 0.02
675
3

21

Difficult

Which of the following is not a source of ignition?


Electrical switch
An Ex-certified fan motor
Light switch
Open mechanical pressure switch

22

Difficult

What is R290?


Butane
Propene
Propylene
Propene

23

Difficult

According to EN 378, what is the maximum HC refrigerant charge for a display unit (hermetic system with an internal condenser) located in the ground-floor shopping area of a supermarket?


2.5 kg
1.5 kg
150 g
1.0 kg

24

Difficult

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


Current consumption differs for compressors using flammable refrigerants compared to those using HFCs
The method of starting the compressor motor differs from that used with HFCs
It could be a source of ignition
A relay is never required for compressors using flammable refrigerants

25

Difficult

What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?


1 m
3 m
10 m
5 m

26

Difficult

What is the safe charge for a recovery cylinder with R290 refrigerant, if it can be charged with 10 kg of R404A?


8 kg
20 kg
3.6 kg
17 kg

27

Difficult

How can a vacuum pump be used safely to evacuate a system containing R290?


Position the vacuum pump 3 metres above floor level
Use an ATEX-certified vacuum pump in a well-ventilated area
Fit a long hose to the pump outlet to remove HC away from the system
There is no need to evacuate systems containing R290

28

Difficult

In accordance with ADR regulations, what protective equipment must you have in your vehicle when transporting flammable refrigerants?


Tinted safety goggles
Thick gloves
Fire blanket
A fire extinguisher

29

Difficult

How do you ensure it is safe to light the torch needed to desolder joints in a system that has been evacuated of flammable refrigerant?


Purge the system with oxygen-free nitrogen
You must not desolder joints on a system containing a flammable refrigerant; they must be cut using a pipe cutter
Ensure the area is well ventilated and use a flammable gas detector to check the area
Work outdoors

30

Difficult

How would you remove the refrigerant from a system containing 100 g of R1270 so that it is ready for the joints to be desoldered?


Vent the R1270 to the outside; charge the system with nitrogen until an overpressure is reached, vent and evacuate the system twice, charge the system with nitrogen a third time and vent
Vent the R1270 to the outside and drain the system
Recover the R1270 until a vacuum is achieved
Recover the R1270 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g

31

Difficult

Which of the following leak detection methods cannot be used to locate a leak of R290 refrigerant?


Fluorescent dye and a UV lamp
Electronic leak detector for flammable refrigerants
Leak detection foam
Electronic HFC leak detector

32

Difficult

Why can’t recovery stations designed for HFCs be used with R600a?


The oil in the recovery unit is not soluble in R600a
The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure
The recovery unit cannot withstand the working pressure of R600a
It contains ignition sources

33

Difficult

According to EN 378, what is the maximum charge of R1234ze in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R1234ze is 0.303 kg/m³)?


618 kg
6.18 kg
227 kg
2.27 kg

34

Difficult

What type of refrigerant is R32?


Hydrofluorocarbon
Hydrofluoroolefin
Hydrocarbon
Carbon dioxide

35

Difficult

What hazards do A2L refrigerants pose?


Low toxicity, high flammability
Low toxicity, moderate flammability
High toxicity, high flammability
High toxicity, moderate flammability

36

Difficult

What danger is associated with the combustion of HFO or HFC refrigerants?


Phosgene is produced
Citric acid is produced
Nitrous oxide is produced
Hydrogen fluoride is produced

37

Difficult

What is the approximate displacement volume required for a compressor running on R600a compared to one running on R134a to achieve the same cooling capacity?


Seven times
Twice
The same
Half

38

Difficult

What is the GWP value for R32?


675
0
3
7

39

Difficult

Why is the accuracy of the charge weight more important for systems critically charged with R290 compared to those using HFCs


Because these systems never have liquid receivers
Because R290 is only used in systems with a charge of less than 150g
Due to lower operating pressures
The charge mass is significantly lower than in an HFC system, as the density is much lower

40

Difficult

Why does the condenser fan run continuously in some systems using R1270?


To dilute the refrigerant in the event of a leak
To ensure that the discharge pressure never becomes excessive
To reduce energy consumption
To prevent the build-up of contaminants in the condenser

41

Difficult

What must be included on the label of a cylinder containing a flammable refrigerant?


Net weight only
The name of the refrigerant, the hazard symbol and basic safety information
Information about the cylinder owner
Agent name only

42

Difficult

Why does the absence of a ‘flammable agent’ label on the system pose a significant hazard?


It may lead to the incorrect selection of oil
It may lead to the use of tools that are a source of ignition
It reduces the system’s efficiency
It has no significant impact on safety

43

Difficult

Which set of information on the label of a flammable agent cylinder is crucial from a safety perspective?


Gross weight and batch number
Name of the substance, hazard pictogram, UN number
Cylinder colour and date of manufacture
Manufacturer’s name and country of origin

44

Difficult

What is the requirement regarding the labelling of an installation containing a flammable substance?


Labelling is not required for hermetically sealed systems
The labelling must indicate the type of substance and the flammability hazard
Colour-coding of pipes is sufficient
Labelling is required only in technical rooms

45

Difficult

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


Risk of leakage and the formation of an explosive mixture
No impact on safety
Merely a reduction in efficiency
Merely installation difficulties

46

Difficult

What is the purpose of installing gas detectors in a room with a refrigeration system?


Early detection of refrigerant leaks and prevention of health risks
Measuring the refrigerant temperature
Regulating compressor capacity
Monitoring pipe pressure

47

Difficult

How often should gas detection sensors in the service room be checked?


Only after a leak has occurred
Once every 5 years
Before each start-up of the unit
In accordance with the manufacturer’s instructions and applicable health and safety regulations

48

Difficult

Where should a gas detector be positioned in accordance with EN 378?


Only at the entrance to the room
Near the control panel
Anywhere in the room
On the ceiling if the gas is lighter or heavier than air; near the floor if it is lighter or heavier

49

Difficult

How should an employee respond when a gas alarm is triggered?


Switch off the system and wait for the alarm to stop
Reduce the pressure in the system
Leave the room immediately and notify their supervisor
Carry on working until they see a leak

50

Difficult

What safety checks should be carried out when installing a new refrigeration system?


Is the air filter new?
The colour of pipes and hoses
The presence of health and safety signage, adequate ventilation and gas detectors
Only the compressor power

51

Difficult

Gas detectors should be installed in rooms where:


The room is less than 5 m²
The amount of refrigerant exceeds a specified permissible threshold
Any refrigerant is present, regardless of the quantity
Ventilation is natural

52

Difficult

What is the minimum number of emergency exits in a plant room (refrigeration plant room) and how should they be signposted?


One exit, clearly marked in the direction of escape
One exit with an information sign about the refrigerant
Exits do not need to be signposted if the room is small
At least two exits, but signage is optional

53

Difficult

Which measure, when installing a system using a flammable refrigerant, improves its energy efficiency?


No leak test
Restriction of ventilation
Thorough leak testing and vacuuming
Increasing the refrigerant charge

54

Difficult

How do leaks affect systems using flammable refrigerants?


They cause refrigerant loss, reduced efficiency and a fire hazard
They lower the temperature
Have no effect
They improve efficiency

55

Difficult

Why is it important to limit the amount of refrigerant in HC systems?


It increases efficiency
It has no effect
It lowers the temperature
It reduces the risk of explosion and improves the system’s operational safety

56

Difficult

Why is the cleanliness of heat exchangers in HC systems important?


It doesn’t matter
Causes leaks
It increases the pressure
It improves heat transfer and reduces energy consumption

57

Difficult

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Regular checks for leaks and operating parameters
Increasing the refrigerant charge
Disabling safety devices
Lack of servicing

58

Difficult

How does the correct selection of components affect a system using a flammable refrigerant?


It lowers the temperature
It ensures safe and optimal operation and minimises energy losses
It increases the amount of refrigerant
It doesn’t matter

59

Difficult

Why is it important to use the correct service tools in HC systems?


It doesn’t matter
It ensures operational safety and reduces refrigerant losses
Causes leaks
It increases energy consumption

60

Difficult

How does pipe insulation affect the efficiency of systems containing HC?


Causes leaks
It reduces energy losses and improves efficiency
It increases the pressure
It doesn’t matter

61

Difficult

What hazards are associated with a Class A3 safety agent?


High flammability, lower toxicity
Slightly flammable, lower toxicity
High toxicity, does not propagate flames
Lower toxicity, does not propagate flames

62

Difficult

18 What is the GWP of R32 (according to AR4)?


675
0
6
3945

63

Difficult

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Practical limit, height of the indoor unit, floor area
Lower flammability limit, height of the indoor unit, floor area
Practical limit, room volume
Lower flammability limit, room volume

64

Difficult

What compressor displacement is required for R1270, relative to R404A compressors for the medium-temperature range (cold store)?


600%
50%
150%
Similar